Treatment Process Description
ExtremeSTPs utilize aerobic treatment inserts manufactured by Bio-Microbics®,
Inc. The FAST® process begins with pretreatment to remove floating
and settling solids by trapping them in an anaerobic settling zone.
This step is followed by aerobic biological fixed activated sludge
(FAST®) treatment in a compartment with a submerged growth media
that is colonized by the microbes that are naturally present in sewage.
A blower forces air into an airlift pump inside the FAST® unit.
The airlift pump vigorously mixes the air with the sewage and circulates
the aerated sewage through channels in the growth media. This brings
oxygen and nutrients into contact with the microbes that are attached
to the growth media so that they can decompose the impurities. Nitrification
occurs in the aerobic zone, and as the airlift pump circulates the
water, a small percentage of the water continuously returns to the
anaerobic zone where denitrification occurs.
FAST® units can be purchased as modules that can be fitted into
fiberglass, steel, or concrete tanks to meet a wide variety of treatment
applications. Individual FAST® units are available in sizes ranging
from 150 gallons per day (gpd) to 9,000 gpd. Several units can be
manifolded together in series or parallel configurations to treat
greater flows. The Bio-Microbics®, Inc. link on this website has
further information about FAST® systems.
Lifewater Engineering Company's ExtremeSTPs begin with the two steps
described above, namely pretreatment and aerobic FAST® treatment.
However, in order for the systems to work in cold climates two additional
steps must be taken.
Before treated effluent is discharged onto the ground surface or into
a water body, it must be disinfected. In ExtremeSTPs this is generally
done using either UV or chlorination. Most of the smaller system use
UV and the larger systems use chlorination. A dechlorination step
can be added if needed.
Effluent flow control prevents effluent from trickling out the effluent
line and freezing in the line itself or on the ground close to the
point of discharge. Whenever site conditions will allow, flow control
is done using an automatic dosing siphon. This device has no moving
parts except water and air, yet it retains treated effluent in the
ExtremeSTP until a preset amount is accumulated and the siphon is
triggered. Then effluent is then discharged rapidly (30 gpm on the
smaller systems) until the liquid in the effluent compartment drops
to the level where siphoning stops. In this way, relatively large
doses of warm effluent are discharged onto a splash plate (to prevent
erosion) and the effluent soaks into the natural vegetative mat and
flows away from the treatment plant before it freezes.
In cases where there is insufficient head to allow use of a dosing
siphon, an effluent pump is used to achieve about the same dosing
rate and volume while lifting the effluent to a suitable discharge
location. Discharge can also go to a leach field either with or without
a dosing siphon or effluent pump. Systems can be customized to suit
particular site conditions.
Hydraulic Loading
All wastewater treatment systems must be sized to handle both the
hydraulic and organic loadings to which they will be subjected. Since
ExtremeSTPs use aerobic treatment inserts manufactured by Bio-Microbics®,
Inc., the hydraulic capacities of ExtremeSTPs are determined by the
hydraulic capacities of the Bio-Microbics treatment inserts.
Bio-Microbics' model numbers designate hydraulic capacities in thousands
of gallons per day. For example their Model MCF0.5 treatment insert
is rated at 0.5 thousand gallons (or 500 gallons) per day and their
Model MCF9.0 is rated at 9,000 gallons per day. ExtremeSTP model numbers
designate hydraulic capacity in gallons per day. For example, a Model
XSTP500 system is rated at 500 gallons per day.
Fixed activated sludge treatment (FAST®) systems can process surge
flows very well. In FAST® systems, the microbes that decompose
the organic matter are fixed on a growth medium rather than suspended
in the liquid. Sludge cannot wash out of the clarifier because there
is no clarifier. There is a large reserve of treated wastewater inside
the FAST® insert and when more sewage enters the treatment plant,
an equal amount of treated wastewater is displaced out.
If actual flows are not available, conventional engineering techniques
should be used to estimate or predict flows as closely as possible.
However, excessive efforts need not be made to refine a flow estimate
because in most cases it is not hydraulic capacity that determines
which system should be used.
Organic Loading
The organic capacities of ExtremeSTPs are determined by the organic
capacities of the Bio Microbics treatment inserts that are used, and
in most cases, especially with modern water-saving fixtures, it is
organic loading that determines which size system must be used. Bio-Microbics®
rates their residential systems in terms of a range of people they
will handle. However, when applying their numbers you must keep in
mind that the high end of the range represents a short-term peak rather
than a long-term average number of people. If necessary, these numbers
can be approximately converted to lbs of BOD5 per day by multiplying
the average of the range of persons per module times the typical factor
of 0.2 lbs BOD5 per person per day.
Discharge
If possible, the first choice for discharge of treated effluent from
any on-site sewage treatment system is a subsurface soil absorption
system. Soil absorption systems should be designed in accordance with
generally accepted practices for the local area in which the treatment
system will be located. However, since ExtremeSTPs produce an oxygen-rich
effluent with low suspended solids and low BOD5, design of the absorption
system can be based solely on the hydraulic capacity of the soil.
This means that reductions in absorption system size from what is
typically required for a septic system (perhaps up to 50 percent)
can sometimes be achieved.
However, since ExtremeSTPs were originally designed for permafrost
areas where discharge into the ground is not practical, surface discharge
is commonly done from ExtremeSTPs. In Alaska, each discharge location
must be approved by the regulatory body (typically the Alaska Department
of Environmental Conservation) on a case-by-case basis as part of
the plan approval process.
We have found that surface discharge works best where there is a thick,
natural, well-drained vegetative mat. In the Interior of Alaska, black
spruce forests provide an ideal environment. If permafrost is an issue,
the discharge location should not be close to a foundation or other
structure that could be damaged by thermokarsting (ground subsidence
due to thawing of unstable permafrost). If thermokarsting is a concern,
we recommend use of a thermo siphon under the ExtremeSTP and possibly
underneath the point of surface discharge.
An automatic dosing siphon is used to prevent effluent from freezing
in the discharge pipe or at the point of discharge on top of the ground.
The dosing siphon has no moving parts other than the air and water
within it, yet it retains effluent in the effluent compartment until
it rises to a predetermined level. At that point, a rapid discharge
begins and continues until the level drops to the point where the
siphoning action is broken and the discharge from the effluent compartment
abruptly stops. After the water in the effluent pipe drains, essentially
no more is discharged until the next dose occurs. On sloping ground
where permafrost is not a problem but soil conditions are poor and
a soil absorption system will not work, consider using a below ground
system with an above ground discharge.
Elevation Requirements
USTP500, USTP750, and USTP900 models without an effluent dosing siphon
have a 3 to 5-inch drop from the 4-inch inlet pipe to the 4-inch outlet
pipe.
USTP500, USTP750, and USTP900 models with an effluent dosing siphon
have an additional 16-inch drop, for a total drop of 20 to 22 inches
from the center of the 4-inch inlet pipe to the center of the 2-inch
outlet pipe.
XSTP150 and XSTP500 models come standard with an effluent dosing siphon.
These models have a 20 to 22-inch drop from the center of the 4-inch
inlet pipe to the center of the 2-inch outlet pipe.
If an effluent pump option is chosen, elevation is typically of minimal
concern.
A drawing and table showing tank dimensions and inlet and outlet elevations
appear at the end of this page.
Inlet & Outlet Piping
Lifewater Engineering Company recommends that the inlet and outlet
pipes be insulated with 2 to 3 inches of polyurethane foam with a
k-factor of about 0.17 BTU/hr/ft2/ºF. The foam should be protected
from damage by UV rays, animals, etc., especially where it is exposed
above ground. We also recommend that the effluent line be heat traced.
Movement of buildings, pipe supports, and the sewage treatment system
can be expected, especially in above ground installations on permafrost.
Projected movement should be taken into consideration when designing
pipe slopes. For example, when an above ground system is set on top
of a thawed active layer, one would expect the treatment system to
rise somewhat when the ground freezes, especially if a thermosyphon
is used to enhance freezing. In this case, the slope of the sewer
line should be set slightly greater than ¼-inch per foot to
accommodate the expected movement.
Inlet and outlet piping connections to the ExtremeSTP should be made
with rubber couplers with stainless steel bands. These will accommodate
some movement between the treatment system and the pipes and will
provide "weak points" at the inlet and outlet so that neither
the pipes nor the treatment plant will be damaged if movement is severe.
Venting Requirements
Because air is pumped into the ExtremeSTP air must be vented out.
ExtremeSTPs are constructed so that there is a common air space above
all of the internal compartments. For residential and small commercial
systems, this air space is commonly vented through the sewer line
and out the main stack vent on the roof of the house or building being
served. We have found that homeowners like this venting system because
it helps keep the roof vent from freezing shut during the winter.
Larger systems, whether residential or commercial will require separate
venting to the atmosphere. Vent diameters must be in accordance with
Bio-Microbics'® specifications for each particular model (see
links page).
Electrical Requirements
ExtremeSTPs are typically constructed so that there is one point of
power connection for the whole unit. For the XSTP150, XSTP500, XSTP750,
and XSTP900 gpd models, one 20 Amp, ground-fault protected circuit
that is dedicated to the ExtremeSTP is normally all that is required,
unless the owner wants a separate ground-fault protected circuit for
alarm purposes, such as for a high water alarm.
Permafrost Considerations
For sites with permafrost, the engineer should consider use of a thermosyphon
to enhance freezing in the ground. In every case where a thermosyphon
has been used, the treatment system has stayed in place and level.
In one case, the yard underwent extensive thermokarsting and the house
needed frequent leveling, yet the treatment plant remained in position
because a thermosyphon kept the ground frozen.
Typically, above ground systems can be installed at any time of year
because minimal excavation is required. When installing on permafrost,
the best time of year may be in the fall or early winter. At this
time of year, only the surface of the active layer has refrozen, so
the ground is easy to excavate to prepare a pad for the system, yet
it freezes at night, thereby facilitating equipment operation.
Foundation thoughts for permafrost areas:
The best rule for permafrost areas is this: Do not rely only on these
general thoughts to design your tank foundation, rather consult your
"local" foundation expert even if that person is 1000 miles
away!
o Place on mineral soil - ExtremeSTPs should be placed either on an
insulated gravel pad (such as is often constructed for a building
on permafrost) or on mineral soil. In permafrost areas, it is best
to place the unit in a very small clearing shaded by trees (such as
black spruce). The natural vegetative mat under the tank foundation
should be removed so that it does not compress later causing the tank
to shift. If the vegetative mat is removed, it should only be removed
under the tank foundation and should be left in place undisturbed
everywhere else to preserve ground insulation and minimize permafrost
thaw.
o Leave an air space - When installing an XSTP on permafrost consider
leaving an air space underneath the tank. This will allow cold air
to flow under the tank in winter and reduce ground temperatures so
that it is less likely to thaw during the warmer months. One way to
do this is with a pressure treated timber foundation.
o Pressure-treated timber foundation - This type of foundation eliminates
direct contact between the tank and the permafrost soil, thus reducing
heat flow into the ground. We suggest using 3"x12" or 4"x12"
timbers that are specially treated and rated for ground contact. Since
soil moves seasonally, especially in permafrost areas, consider a
timber arrangement similar to that shown below that will allow shims
to be paced between the timbers as needed to keep the tank level.
See conceptual sketch below.
o Extra 2 inches of rigid foam - When the tank must be in direct contact
with the ground, consider placing 2 inches of rigid foam between the
tank and the ground to slow heat transfer into the ground.

(Note: the above sketch is intended only to convey the concept of
a timber foundation. It is not a design drawing!)
Thermosyphon - If your property is already experiencing thermokarsting
due to permafrost thaw, or if you prefer to take the conservative
approach (which we recommend) you should install a thermosyphon underneath
the tank to help refreeze the ground and/or keep it frozen. Consult
a local foundation engineer or Arctic Foundations in Anchorage, Alaska
(1-907-562-2741, www.arcticfoundations.com) for further information
and advice.
Flat loop evaporator for thermosyphon - When you are uncertain of
the need for a thermosyphon but want to maintain the option of having
one if necessary, we recommend you install a flat loop evaporator
beneath the tank or timber foundation at the time of installation.
This can be done at a small extra cost and will allow a condenser
and gas/liquid charge (the expensive parts of a thermosyphon) to be
added later if necessary. Keep in mind that if you know you'll need
a thermosyphon, it is generally less expensive to install a standard
thermosyphon initially than to install just the flat loop evaporator
first and the condenser and gas/liquid charge later. Some suggested
generic installation instructions appear below, but we recommend that
you contact a local foundation engineer or Arctic Foundations in Anchorage,
Alaska (1-907-562-2741, www.arcticfoundations.com) for further information
and site specific recommendations.
Flat loop evaporator installation instructions:
For model XSTP150, XSTP500, XSTP750, and XSTP900 systems, use 60 feet
of ½-inch diameter Type K copper tubing for the evaporator.
Solder a cap onto each end of the tubing before taking it out of a
clean environment. It is important that the inside of the tubing remain
completely clean and dry.
Before setting the tank or its foundation, bed the tubing in 6 inches
of sand, with 3 inches of sand below and 3 inches above the tubing.
Set the tubing so that both ends are together and extend up to near
the top edge of the tank. The rest of the tubing should loop back
and forth under the tank so as to get the best coverage (see sketch
below). Compact the sand carefully so as not to damage the tubing.
Set the tank or its foundation on top of the compacted sand and secure
the ends of the tubing near the top edge of the tank so that a condenser
can later be connected to it. Leave the soldered caps in place on
the ends of the tubing until they are removed by the technician who
installs the condenser.

Installation & Field Assembly
Installation is normally done by a certified on-site sewage system
installer and is not included in Lifewater's pricing. Installation
includes setting the unit in place, running the sewer pipe from the
house to the unit, running the outlet pipe from the unit to the point
of discharge, and providing electrical power to the unit. A homeowner
who is familiar with applicable building codes and normally does his/her
own wiring and plumbing can in most cases install a system (if this
is allowed in your jurisdiction).
ExtremeSTPs are shop assembled as much as possible, but depending
on how and where they will be shipped some field assembly may be required.
For below ground units, some field assembly is always required. When
the units are being installed at a location close to a distributor,
such as near Fairbanks, Anchorage, or Kenai, Alaska, field assembly
of ExtremeSTP components is typically included in the sales price.
Please ask about this when ordering a system.
Handling ExtremeSTPs
XSTP models (above ground fiberglass tanks) should only be picked
up using either a forklift with extended forks, a boom and two or
more fabric straps, or a fabric sling designed for the purpose. Cables,
chains, or other methods that could damage the fiberglass should never
be used. Steel USTP models (underground steel tanks) typically have
a lifting ring or rings welded onto the top. These steel tanks should
be picked from above by means of the lifting rings.
Approximate tank dimensions &
inlet & outlet pipe elevations:

| Model |
A - Inlet Height (inches)
|
B - Outlet Height (inches)
|
Outlet Diameter (inches)
|
L - Length (inches)
|
Width (inches)
|
Tank Height (inches)
|
|
XSTP150UVD
|
45
|
30
|
2
|
96
|
48
|
52
|
|
XSTP500UVD
|
57
|
36
|
2
|
100
|
69
|
72
|
|
XSTP750/900UVD
|
~
|
-
|
2
|
-
|
-
|
-
|
|
USTP500
|
50
|
47
|
4
|
120
|
58
|
58
|
|
USTP500
D
|
~
|
35
|
2
|
169
|
62
|
63
|
|
USTP500
|
~
|
-
|
2
|
169
|
62
|
63
|
|
USTP750 or 900
|
54.5
|
45*
|
2
|
144
|
82
|
58
|
|
USTP750 or 900
D
|
~
|
2
|
2
|
169
|
63
|
63
|
| USTP750 or 900
P |
54.5
|
36*
|
2
|
129
|
63
|
73
|
| Other models |
(please ask for dimensions on larger and
custom models)
|
Notes
- All inlet diameters (except larger models) are 4 inches
- D means automatic dosing siphon
- P means effluent pump
-
means with or without disinfection
- No suffix means no disinfection, no dosing siphon, no pump
- * means dimension can be specified at time of ordering
- XSTP (above ground) models come standard with an automatic dosing
siphon but can be ordered with an effluent pump
- All dimensions subject to change without notice